UPSCODE2(8) | NUT Manual | UPSCODE2(8) |
NAME¶
upscode2 - Driver for UPScode II compatible UPS equipmentNOTE¶
This man page only documents the hardware-specific features of the upscode2 driver. For information about the core driver, see nutupsdrv(8).SUPPORTED HARDWARE¶
This driver supports UPS equipment which can be controlled via the UPScode II protocol. This is mainly Fiskars, Powerware equipment, but also some (probably OEM’ed) products from Compaq.EXTRA ARGUMENTS¶
This driver supports the following optional settings in the ups.conf(5): manufacturer=valueAutodetection of this parameter is not
possible yet (and it probably never will be). Therefore, this user-defined
string accepts any name. The default is unknown.
input_timeout=value
The timeout waiting for a response from the
UPS. Some UPS models have shown to be rather slow, resulting in frequent
messages about empty responses from the UPS. If you see this, try increasing
this value.
output_pace=value
Delay between characters sent to the UPS. This
was added for completeness with the above parameter. It has not shown to be
needed yet.
baudrate=value
The default baudrate is 1200, which is the
standard for the UPScode II protocol.
full_update_timer=value
Number of seconds between collection of
normative values.
use_crlf
Flag to set if commands towards to UPS need to
be terminated with CR-LF, and not just CR.
use_pre_lf
Flag to set if commands towards to UPS need to
be introduced with an LF. A Compaq T1500h is known to need this.
COMMANDS¶
The driver supports the following commands for those UPSen that support them. The available commands are autodetected during initialization, so you should check availability with upscmd -l.•test.panel.start - Start UPS self
test
•test.battery.start - Start battery self
test
•beeper.enable - Enable UPS beeper
•beeper.disable - Disable UPS
beeper
•shutdown.return - Shut down in 1 second
and wait for power to return
•shutdown.stayoff - Shut down in 1
seconds
•shutdown.reboot - Shut down in 1
seconds and reboot after 1 minute
•shutdown.reboot.graceful - Shut down in
20 seconds and reboot after 1 minute
NOTES¶
The Powerware UPS models that this driver has been tested against until now have not returned a value for battery.charge. Therefore, the driver will guestimate a value based on the nominal battery min/max and the current battery voltage.AUTHOR¶
Håvard Lygre <hklygre@online.no>, Niels Baggesen <niels@baggesen.net>SEE ALSO¶
The core driver:¶
nutupsdrv(8)Internet resources:¶
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/05/21/2012 | Network UPS Tools |