NAME¶
safenet - Driver for SafeNet compatible UPS equipmentNOTE¶
This man page only documents the hardware-specific features of the safenet driver. For information about the core driver, see nutupsdrv(8).SUPPORTED HARDWARE¶
This driver supports UPS equipment which can be controlled via SafeNet v1.0 for Windows (serial interface only).EXTRA ARGUMENTS¶
This driver supports the following optional settings in the ups.conf(5) file: manufacturer=valueAutodetection of this parameter is not
possible yet (and it probably never will be). Therefore, this user-defined
string accepts any name. The default is unknown.
modelname=value
Like manufacturer above. The default is
unknown.
serialnumber=value
Like manufacturer above. The default is
unknown.
ondelay=value
Time to wait before switching on the UPS
(minutes). Defaults to 1 minute.
offdelay=value
Time to wait before shutting down the UPS
(seconds). Defaults to 30 seconds.
UPSCMD¶
This driver supports some instant commands (see upscmd(8)): test.battery.startStart UPS self test
test.battery.stop
Cancel UPS self test
test.failure.start
Start simulated power failure
test.failure.stop
Cancel simulated power failure
beeper.enable
Enable the UPS beeper
beeper.mute
Temporarily mute the UPS beeper
beeper.toggle
Toggle the UPS beeper
shutdown.return
Turn off the load and wait for the power to
return. Uses the timer defined by offdelay.
shutdown.reboot
Turn off the load and return. Uses the timers
defined by offdelay and ondelay.
KNOWN PROBLEMS¶
If you run the shutdown.return command with mains present, the output may stay on or switch off and not back on again. The shutdown.reboot command will unconditionally switch on the load again (with or without mains present).AUTHOR¶
Arjen de Korte <adkorte-guest at alioth.debian.org>SEE ALSO¶
The core driver:¶
nutupsdrv(8)Internet resources:¶
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/05/21/2012 | Network UPS Tools |