UPS.CONF(5) | NUT Manual | UPS.CONF(5) |
NAME¶
ups.conf - UPS definitions for Network UPS ToolsDESCRIPTION¶
This file is read by the driver controller upsdrvctl(8), the UPS drivers that use the common core (see nutupsdrv(8), and upsd(8)). The file begins with global directives, and then each UPS has a section which contains a number of directives that set parameters for that UPS. A UPS section begins with the name of the UPS in brackets, and continues until the next UPS name in brackets or until EOF. The name "default" is used internally in upsd, so you can’t use it in this file. You must define the driver and port elements for each entry. Anything after that in a section is optional. A simple example might look like this:[myups] driver = blazer_ser port = /dev/ttyS0 desc = "Web server UPS"
[bigups] driver = apcsmart port = /dev/cua00 cable = 940-0095B sdtype = 2 desc = "Database server UPS"
GLOBAL DIRECTIVES¶
chrootOptional. The driver will chroot(2) to this directory
during initialization. This can be useful when securing systems.
driverpath
Optional. Path name of the directory in which the UPS
driver executables reside. If you don’t specify this, the programs look
in a built-in default directory, which is often /usr/local/ups/bin.
maxstartdelay
Optional. Same as the UPS field of the same name, but
this is the default for UPSes that don’t have the field.
maxretry
Optional. Specify the number of attempts to start the
driver(s), in case of failure, before giving up. A delay of retrydelay
is inserted between each attempt. Caution should be taken when using this
option, since it can impact the time taken by your system to start.
The default is 1 attempt.
retrydelay
Optional. Specify the delay between each restart attempt
of the driver(s), as specified by maxretry. Caution should be taken
when using this option, since it can impact the time taken by your system to
start.
The default is 5 seconds.
pollinterval
Optional. The status of the UPS will be refreshed after a
maximum delay which is controlled by this setting. This is normally 2 seconds.
This may be useful if the driver is creating too much of a load on your system
or network.
user
Optional. If started as root, the driver will setuid(2)
to the user id associated with username.
UPS FIELDS¶
driverRequired. This specifies which program will be monitoring
this UPS. You need to specify the one that is compatible with your hardware.
See nutupsdrv(8) for more information on drivers in general and
pointers to the man pages of specific drivers.
port
Required. This is the serial port where the UPS is
connected. On a Linux system, the first serial port usually is
/dev/ttyS0. On FreeBSD and similar systems, it probably will be
/dev/cuaa0.
sdorder
Optional. When you have multiple UPSes on your system,
you usually need to turn them off in a certain order. upsdrvctl shuts down all
the 0s, then the 1s, 2s, and so on. To exclude a UPS from the shutdown
sequence, set this to -1.
The default value for this parameter is 0.
desc
Optional. This allows you to set a brief description that
upsd will provide to clients that ask for a list of connected equipment.
nolock
Optional. When you specify this, the driver skips the
port locking routines every time it starts. This may allow other processes to
seize the port if you start more than one accidentally.
You should only use this if your system won’t work without it.
This may be needed on Mac OS X systems.
ignorelb
Optional. When you specify this, the driver ignores a low
battery condition flag that is reported by the UPS (some devices will switch
off almost immediately after setting this flag, or will report this as soons
as the mains fails). Instead it will use either of the following conditions to
determine when the battery is low:
The idea is to set the battery.charge.low and/or battery.runtime.low levels in
ups.conf to a value that gives enough time to cleanly shutdown your
system:
In order for this to work, your UPS should be able to (reliably) report charge
and/or runtime remaining on battery. Use with caution!
maxstartdelay
battery.charge < battery.charge.low battery.runtime < battery.runtime.low
override.battery.charge.low = 30 override.battery.runtime.low = 180
Optional. This can be set as a global variable above your
first UPS definition and it can also be set in a UPS section. This value
controls how long upsdrvctl will wait for the driver to finish starting. This
keeps your system from getting stuck due to a broken driver or UPS.
The default is 45 seconds.
default.<variable>
Optional. Set a default value for <variable> which
is used in case the UPS doesn’t provide a value, but will be
overwritten if a value is available from the UPS:
The above will report the nominal input voltage to be 230, unless the UPS tells
us differently.
override.<variable>
default.input.voltage.nominal = 230
Optional. Set a value for <value> that overrides
any value that may be read from the UPS. Used for overriding values from the
UPS that are clearly wrong (some devices report wrong values for battery
voltage for instance):
Use with caution! This will only change the appearance of the variable to the
outside world, internally in the UPS the original value is used.
All other fields are passed through to the hardware-specific part of the driver.
See those manuals for the list of what is allowed.
override.battery.voltage.nominal = 12
INTEGRATION¶
upsdrvctl(8) uses this file to start and stop the drivers. The drivers themselves also obtain configuration data from this file. Each driver looks up its section and uses that to configure itself. upsd(8) learns about which UPSes are installed on this system by reading this file. If this system is called "doghouse" and you have defined a UPS in your ups.conf called "snoopy", then you can monitor it from upsc(8) or similar as "snoopy@doghouse".SEE ALSO¶
upsd(8), nutupsdrv(8), upsdrvctl(8)Internet resources¶